Message displayed on the remote control: DOOR SENSOR or DOOR SENSOR OPEN SEE MICROSWITCH
The SIC44 is the shutdown triggered by the microswitch when the front door or the pellet door remains open for more than 120 seconds.
Actions to take:
Clear the error and check that the front door and the pellet tank door close properly, ensuring that they activate their respective microswitches.
If necessary, adjust the position of the microswitch, moving it as close as possible to the door to prevent any thermal expansion during operation from preventing proper closing and the consequent contact of the microswitch.
If the error persists, check the wiring (The contact is normally closed, the door microswitch must be connected to fastons 11 and 14). Replace the microswitch in case of malfunction after proper testing with a tester.