You can download the dedicated Intelligent Tank manual within the reserved area “boutique/technical service centers,” using the following access credentials:
- Username: moretti-design-en
- Password: boutique-cat-en
Below are the wiring and configuration of the parameters necessary for enabling the Tank.
To enable the system, connect the Tank auger to terminals 5 and 6 of the control unit. The pellet level sensor must be connected with the black wire to terminal 59, brown to 58, red to 43.
Then, access the system menu and set the following parameters:
- Settings:
- P44 = 2 (V2 Output Configuration)
- P84 = 6 (IN13 Input Configuration)
- Timings:
- T23 = 20 [min]
Indicates the waiting time (in minutes) that must pass from the uncovering of the pellet level sensor before the Tank auger loading is activated. The stove must be in the “Normal” state.
This value can be reduced according to the system’s needs. - T24 = 3600 [s]
Activation time (in seconds) of the auger for pellet loading.