Function:
Automatically disables the secondary source (e.g., gas boiler) when the pellet stove/boiler is sufficiently hot.
⚙️ Electrical connections
- Thermostatic output (A5)
- PIN 25 = COM
- PIN 26 = NO
- Type: dry contact (no voltage)
🧠 Operating logic
When the water temperature exceeds the threshold:
- Sensor: Th56 (default: 45 °C)
- Action: contact activation → secondary source blocking
👉 In practice:
If the pellet stove is already heating, the secondary source does not start.
📋 Parameters to set
- P46 = 3 → enables inhibition function
- Th56 → temperature threshold (default 45 °C)
🔄 Contact configuration (A95)
Defines the relay behavior:
- A95 = 0 → NO (normally open) contact
→ closes when temperature is exceeded - A95 = 1 → NC (normally closed) contact
→ opens when temperature is exceeded